Kita duwe klompok efisiensi sing mumpuni kanggo menehi dhukungan sing apik kanggo klien kita.Kita biasane ngetutake prinsip berorientasi pelanggan, fokus rincian kanggo Pasokan OEM / ODM 4 Inti XLPE Insulated PVC Sheathed Unarmoured Power Cable / Fleksibel Flame Retardant Power Cable, Saiki, kita ngupayakake kerjasama sing luwih gedhe karo para panuku ing luar negeri sing ditemtokake kanthi bebarengan keuntungan.Mangga aran gratis kanggo hubungi kita kanggo rincian liyane.
Kita duwe klompok efisiensi sing mumpuni kanggo menehi dhukungan sing apik kanggo klien kita.Biasane kita tindakake prinsip customer-oriented, rincian-fokus kanggoKabel Tembaga China lan Tembaga Insulated PVC, Kanthi netepi prinsip "oriented manungsa, menang kanthi kualitas", perusahaan kita kanthi tulus nampani pedagang saka ing omah lan ing luar negeri kanggo ngunjungi kita, ngobrol bisnis karo kita lan bebarengan nggawe masa depan sing apik.
Aplikasi
Trunking kabel njero ruangan, njaba kanggo stasiun listrik, industri lan switchgear uga kanggo jaringan pasokan kutha, yen karusakan mekanis ora mungkin.
Konstruksi
Karakteristik
Dirating voltase: 0.6/1kV
1. sak operasi normal kabel, suhu konduktor maksimum kudu 70 ℃ kanggo PVC jampel lan 90 ℃ kanggo XLPE jampel.
2. Suhu maksimum konduktor sajrone sirkuit cendhak (durasi maksimal ora ngluwihi 5 detik): Insulasi PVC - 160 ℃ kanggo bagean konduktor ≤300mm2, 140 ℃ kanggo bagean salib konduktor> 300mm2;Crosslinked PVC insulasi ing 250 ℃.
3. Nalika mbikak kabel, suhu sekitar ora bakal kurang saka 0 ℃, lan minimal allowable mlengkung radius minangka nderek:
Kabel inti tunggal: 20D tanpa lapis baja, 15D lapis baja
Kabel multi-inti: 15D kanggo unarmored, 12D kanggo armored
Where: D- diameteripun njaba kabel.
4. Kabel putus gaya:
Kabel inti aluminium: 40 × S (N)
Kabel inti tembaga: 70 × S (N)
Cathetan: S yaiku total area cross-sectional konduktor
Standar
IEC 60502-1, GB/T 12706.1
Paramèter
Kabel Daya Inti Tunggal | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
1×1.5 | 0.7 | 1.4 | 6 | 53 | 12.1 | 3.5 | 22 | 33 |
1×2.5 | 0.7 | 1.4 | 6 | 68 | 7.41 | 3.5 | 31 | 43 |
1×4 | 0.7 | 1.4 | 7 | 87 | 4.61 | 3.5 | 41 | 56 |
1×6 | 0.7 | 1.4 | 7 | 110 | 3.08 | 3.5 | 52 | 70 |
1×10 | 0.7 | 1.4 | 8 | 155 | 1.83 | 3.5 | 71 | 94 |
1×16 | 0.7 | 1.4 | 9 | 220 | 1.15 | 3.5 | 92 | 120 |
1×25 | 0.9 | 1.4 | 10 | 345 | 0.727 | 3.5 | 120 | 155 |
1×35 | 0.9 | 1.4 | 12 | 424 | 0.524 | 3.5 | 150 | 185 |
1×50 | 1 | 1.4 | 13 | 555 | 0.387 | 3.5 | 180 | 220 |
1×70 | 1.1 | 1.4 | 14 | 770 | 0.268 | 3.5 | 230 | 270 |
1×95 | 1.1 | 1.5 | 16 | 1040 | 0.193 | 3.5 | 285 | 320 |
1×120 | 1.2 | 1.5 | 18 | 1290 | 0.153 | 3.5 | 335 | 365 |
1×150 | 1.4 | 1.6 | 20 | 1590 | 0.124 | 3.5 | 385 | 410 |
1×185 | 1.6 | 1.6 | 22 | 1944 | 0,0991 | 3.5 | 450 | 465 |
1×240 | 1.7 | 1.7 | 25 | 2510 | 0,0754 | 3.5 | 535 | 540 |
1×300 | 1.8 | 1.8 | 27 | 3042 | 0,0601 | 3.5 | 620 | 610 |
1×400 | 2 | 1.9 | 31 | 3869 | 0.047 | 3.5 | 720 | 695 |
1×500 | 2.2 | 2.1 | 35 | 4910 | 0,0366 | 3.5 | 835 | 780 |
1×630 | 2.4 | 2.2 | 40 | 6220 | 0,0283 | 3.5 | 960 | 880 |
1×800 | 2.6 | 2.4 | 45 | 7870 | 0,0221 | 3.5 | 1110 | 970 |
1×1000 | 2.8 | 2.6 | 51 | 9804 | 0,0176 | 3.5 | 1230 | 1060 |
2 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
2×2.5 | 0.7 | 1.8 | 11.8 | 151 | 7.41 | 3.5 | 26 | 35 |
2×4 | 0.7 | 1.8 | 12.7 | 198 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1.8 | 13.7 | 250 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1.8 | 15 | 374 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1.8 | 17 | 518 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1.8 | 20 | 772 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1.8 | 22 | 1006 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1.8 | 20 | 1365 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1.8 | 21 | 1872 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.8 | 24 | 2475 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 1.8 | 27 | 3089 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 1.9 | 30 | 3834 | 0.124 | 3.5 | 325 | 345 |
3 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×1.5 | 0.7 | 1.5 | 10 | 145 | 12.1 | 3.5 | 20 | 27 |
3×2.5 | 0.7 | 1.5 | 11 | 185 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1.5 | 12 | 250 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1.5 | 13 | 320 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1.8 | 16 | 450 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1.8 | 18 | 640 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1.8 | 21 | 940 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1.8 | 23 | 1260 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1.8 | 23 | 1670 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1.8 | 26 | 2280 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 1.9 | 30 | 3020 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 2 | 32 | 3790 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 2.2 | 37 | 4750 | 0.124 | 3.5 | 325 | 345 |
3×185 | 1.6 | 2.3 | 41 | 5654 | 0,0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 2.4 | 46 | 7243 | 0,0754 | 3.5 | 440 | 450 |
3×300 | 1.8 | 2.6 | 51 | 9465 | 0,0601 | 3.5 | 505 | 515 |
3×400 | 2 | 3 | 64 | 12066 | 0.047 | 3.5 | 570 | 575 |
4 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
4×4 | 0.7 | 1.8 | 13 | 253 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1.8 | 14 | 337 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1.8 | 17 | 501 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1.8 | 20 | 778 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1.8 | 23 | 1160 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1.8 | 25 | 1554 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1.8 | 23 | 2148 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1.8 | 27 | 2928 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.9 | 31 | 3854 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 2 | 33 | 4925 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 2.2 | 38 | 6238 | 0.124 | 3.5 | 325 | 345 |
4×185 | 1.6 | 2.3 | 42 | 7562 | 0,0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 2.5 | 47 | 9836 | 0,0754 | 3.5 | 440 | 450 |
4×300 | 1.8 | 2.6 | 52 | 12550 | 0,0601 | 3.5 | 505 | 515 |
4×400 | 2 | 3.1 | 66 | 15929 | 0.047 | 3.5 | 570 | 575 |
5 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
5×4 | 0.7 | 1.8 | 14.5 | 349 | 4.61 | 3.5 | 34 | 45 |
5×6 | 0.7 | 1.8 | 15.8 | 460 | 3.08 | 3.5 | 43 | 57 |
5×10 | 0.7 | 1.8 | 19 | 699 | 1.83 | 3.5 | 60 | 77 |
5×16 | 0.7 | 1.8 | 22 | 1013 | 1.15 | 3.5 | 83 | 105 |
5×25 | 0.9 | 1.8 | 25 | 1566 | 0.727 | 3.5 | 105 | 125 |
5×35 | 0.9 | 1.9 | 28 | 2083 | 0.524 | 3.5 | 125 | 155 |
5×50 | 1 | 2 | 31 | 2921 | 0.387 | 3.5 | 160 | 185 |
5×70 | 1.1 | 2.1 | 36 | 3974 | 0.268 | 3.5 | 200 | 225 |
5×95 | 1.1 | 2.2 | 39 | 5297 | 0.193 | 3.5 | 245 | 270 |
5×120 | 1.2 | 2.4 | 44 | 6638 | 0.153 | 3.5 | 285 | 310 |
5×150 | 1.4 | 2.5 | 49 | 8290 | 0.124 | 3.5 | 325 | 345 |
5×185 | 1.6 | 2.7 | 55 | 10215 | 0,0991 | 3.5 | 375 | 390 |
5×240 | 1.7 | 3 | 64 | 13130 | 0,0754 | 3.5 | 440 | 450 |
5×300 | 1.8 | 3.2 | 70 | 16670 | 0,0601 | 3.5 | 505 | 515 |
Kabel Daya 3+1 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×4+1×2.5 | 0.7 | 1.8 | 13 | 236 | 4.61 | 3.5 | 34 | 45 |
3×6+1×4 | 0.7 | 1.8 | 14 | 316 | 3.08 | 3.5 | 43 | 57 |
3×10+1×6 | 0.7 | 1.8 | 17 | 461 | 1.83 | 3.5 | 60 | 77 |
3×16+1×10 | 0.7 | 1.8 | 19 | 679 | 1.15 | 3.5 | 83 | 105 |
3×25+1×16 | 0.9 | 1.8 | 22 | 1065 | 0.727 | 3.5 | 105 | 125 |
3×35+1×16 | 0.9 | 1.8 | 24 | 1360 | 0.524 | 3.5 | 125 | 155 |
3×50+1×25 | 1 | 1.8 | 25 | 1901 | 0.387 | 3.5 | 160 | 185 |
3×70+1×35 | 1.1 | 1.9 | 28 | 2585 | 0.268 | 3.5 | 200 | 225 |
3×95+1×50 | 1.1 | 2 | 32 | 3518 | 0.193 | 3.5 | 245 | 270 |
3×120+1×70 | 1.2 | 2.1 | 35 | 4443 | 0.153 | 3.5 | 285 | 310 |
3×150+1×70 | 1.4 | 2.2 | 40 | 5326 | 0.124 | 3.5 | 325 | 345 |
3×185+1×95 | 1.6 | 2.4 | 43 | 8501 | 0,0991 | 3.5 | 375 | 390 |
3×240+1×120 | 1.7 | 2.5 | 48 | 11155 | 0,0754 | 3.5 | 440 | 450 |
3×300+1×150 | 1.8 | 2.7 | 54 | 14470 | 0,0601 | 3.5 | 505 | 515 |
3×400+1×240 | 2 | 3.1 | 66 | 309 | 0.047 | 3.5 | 570 | 575 |
Kabel Daya 3+2 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×4+2×2.5 | 0.7 | 1.8 | 13.9 | 413 | 4.61 | 3.5 | 34 | 45 |
3×6+2×4 | 0.7 | 1.8 | 15.3 | 6682 | 3.08 | 3.5 | 43 | 57 |
3×10+2×6 | 0.7 | 1.8 | 18 | 603 | 1.83 | 3.5 | 60 | 77 |
3×16+2×10 | 0.7 | 1.8 | 21 | 888 | 1.15 | 3.5 | 83 | 105 |
3×25+2×16 | 0.9 | 1.8 | 24 | 1342 | 0.727 | 3.5 | 105 | 125 |
3×35+2×16 | 0.9 | 1.8 | 26 | 1647 | 0.524 | 3.5 | 125 | 155 |
3×50+2×35 | 1 | 1.9 | 29 | 2386 | 0.387 | 3.5 | 160 | 185 |
3×70+2×35 | 1.1 | 2 | 32 | 3201 | 0.268 | 3.5 | 200 | 225 |
3×95+2×50 | 1.1 | 2.1 | 36 | 4269 | 0.193 | 3.5 | 245 | 270 |
3×120+2×70 | 1.2 | 2.3 | 41 | 5437 | 0.153 | 3.5 | 285 | 310 |
3×150+2×70 | 1.4 | 2.4 | 44 | 6519 | 0.124 | 3.5 | 325 | 345 |
3×185+2×95 | 1.6 | 2.5 | 49 | 8101 | 0,0991 | 3.5 | 375 | 390 |
3×240+2×120 | 1.7 | 2.7 | 54 | 10340 | 0,0754 | 3.5 | 440 | 450 |
3×300+2×150 | 1.8 | 2.8 | 56 | 12810 | 0,0601 | 3.5 | 505 | 515 |
Kabel Daya 4+1 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
4×4+1×2.5 | 0.7 | 1.8 | 14.5 | 331 | 4.61 | 3.5 | 34 | 45 |
4×6+1×4 | 0.7 | 1.8 | 15.9 | 435 | 3.08 | 3.5 | 43 | 57 |
4×10+1×6 | 0.7 | 1.8 | 18 | 649 | 1.83 | 3.5 | 60 | 77 |
4×16+1×10 | 0.7 | 1.8 | 21 | 965 | 1.15 | 3.5 | 83 | 105 |
4×25+1×16 | 0.9 | 1.8 | 25 | 1456 | 0.727 | 3.5 | 105 | 125 |
4×35+1×16 | 0.9 | 1.8 | 27 | 1863 | 0.524 | 3.5 | 125 | 155 |
4×50+1×25 | 1 | 1.9 | 29 | 2633 | 0.387 | 3.5 | 160 | 185 |
4×70+1×35 | 1.1 | 2 | 32 | 3565 | 0.268 | 3.5 | 200 | 225 |
4×95+1×50 | 1.1 | 2.1 | 36 | 4735 | 0.193 | 3.5 | 245 | 270 |
4×120+1×70 | 1.2 | 2.3 | 41 | 5977 | 0.153 | 3.5 | 285 | 310 |
4×150+1×70 | 1.4 | 2.4 | 44 | 7276 | 0.124 | 3.5 | 325 | 345 |
4×185+1×95 | 1.6 | 2.5 | 49 | 9055 | 0,0991 | 3.5 | 375 | 390 |
4×240+1×120 | 1.7 | 2.7 | 54 | 11567 | 0,0754 | 3.5 | 440 | 450 |
4×300+1×150 | 1.8 | 3.1 | 66 | 14321 | 0,0601 | 3.5 | 505 | 515 |
Kita duwe klompok efisiensi sing mumpuni kanggo menehi dhukungan sing apik kanggo klien kita.Kita biasane ngetutake prinsip berorientasi pelanggan, fokus rincian kanggo Pasokan OEM / ODM 4 Inti XLPE Insulated PVC Sheathed Unarmoured Power Cable / Fleksibel Flame Retardant Power Cable, Saiki, kita ngupayakake kerjasama sing luwih gedhe karo para panuku ing luar negeri sing ditemtokake kanthi bebarengan keuntungan.Mangga aran gratis kanggo hubungi kita kanggo rincian liyane.