Kabel Daya Tahan Api Tahan Api lan Kabel Daya Tanpa Armour
Kanggo kerep nambah proses manajemen miturut aturan sampeyan "murni, agama sing apik lan kualitas sing apik minangka basis pangembangan perusahaan", kita nemen nyerep inti saka solusi sing gegandhengan sacara internasional, lan kanthi rutin ngasilake barang anyar kanggo nyukupi kabutuhan para pembeli. Flame Retardant Fire Resistant Armored and Unarmoured Power Cable, Kita njaga jadwal pangiriman sing pas, desain modern, kualitas lan transparansi kanggo klien kita.Moto kita bakal menehi solusi kualitas dhuwur ing wektu sing ditemtokake.
Kanggo kerep nambah proses manajemen miturut aturan sampeyan "murni, agama sing apik lan kualitas sing apik minangka basis pangembangan perusahaan", kita nemen nyerep inti saka solusi sing gegandhengan sacara internasional, lan kanthi rutin ngasilake barang anyar kanggo nyukupi kabutuhan para pembeli.China PVC Insulated Power Cable lan Fire-Resistant Power Cable, Pabrik kita dilengkapi fasilitas lengkap ing 10000 meter persegi, sing ndadekake kita bisa gawe marem prodhuksi lan dodolan kanggo solusi bagean otomatis.Kauntungan kita yaiku kategori lengkap, kualitas dhuwur lan rega sing kompetitif!Adhedhasar iku, barang-barang kita entuk pujian sing dhuwur ing omah lan ing luar negeri.
Aplikasi
Trunking kabel njero ruangan, njaba kanggo stasiun listrik, industri lan switchgear uga kanggo jaringan pasokan kutha, yen karusakan mekanis ora mungkin.
Konstruksi
Karakteristik
Dirating voltase: 0.6/1kV
1. sak operasi normal kabel, suhu konduktor maksimum kudu 70 ℃ kanggo PVC jampel lan 90 ℃ kanggo XLPE jampel.
2. Suhu maksimum konduktor sajrone sirkuit cendhak (durasi maksimal ora ngluwihi 5 detik): Insulasi PVC - 160 ℃ kanggo bagean konduktor ≤300mm2, 140 ℃ kanggo bagean salib konduktor> 300mm2;Crosslinked PVC insulasi ing 250 ℃.
3. Nalika mbikak kabel, suhu sekitar ora bakal kurang saka 0 ℃, lan minimal allowable mlengkung radius minangka nderek:
Kabel inti tunggal: 20D tanpa lapis baja, 15D lapis baja
Kabel multi-inti: 15D kanggo unarmored, 12D kanggo armored
Where: D- diameteripun njaba kabel.
4. Kabel putus gaya:
Kabel inti aluminium: 40 × S (N)
Kabel inti tembaga: 70 × S (N)
Cathetan: S yaiku total area cross-sectional konduktor
Standar
IEC 60502-1, GB/T 12706.1
Paramèter
Kabel Daya Inti Tunggal | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
1×1.5 | 0.7 | 1.4 | 6 | 53 | 12.1 | 3.5 | 22 | 33 |
1×2.5 | 0.7 | 1.4 | 6 | 68 | 7.41 | 3.5 | 31 | 43 |
1×4 | 0.7 | 1.4 | 7 | 87 | 4.61 | 3.5 | 41 | 56 |
1×6 | 0.7 | 1.4 | 7 | 110 | 3.08 | 3.5 | 52 | 70 |
1×10 | 0.7 | 1.4 | 8 | 155 | 1.83 | 3.5 | 71 | 94 |
1×16 | 0.7 | 1.4 | 9 | 220 | 1.15 | 3.5 | 92 | 120 |
1×25 | 0.9 | 1.4 | 10 | 345 | 0.727 | 3.5 | 120 | 155 |
1×35 | 0.9 | 1.4 | 12 | 424 | 0.524 | 3.5 | 150 | 185 |
1×50 | 1 | 1.4 | 13 | 555 | 0.387 | 3.5 | 180 | 220 |
1×70 | 1.1 | 1.4 | 14 | 770 | 0.268 | 3.5 | 230 | 270 |
1×95 | 1.1 | 1.5 | 16 | 1040 | 0.193 | 3.5 | 285 | 320 |
1×120 | 1.2 | 1.5 | 18 | 1290 | 0.153 | 3.5 | 335 | 365 |
1×150 | 1.4 | 1.6 | 20 | 1590 | 0.124 | 3.5 | 385 | 410 |
1×185 | 1.6 | 1.6 | 22 | 1944 | 0,0991 | 3.5 | 450 | 465 |
1×240 | 1.7 | 1.7 | 25 | 2510 | 0,0754 | 3.5 | 535 | 540 |
1×300 | 1.8 | 1.8 | 27 | 3042 | 0,0601 | 3.5 | 620 | 610 |
1×400 | 2 | 1.9 | 31 | 3869 | 0.047 | 3.5 | 720 | 695 |
1×500 | 2.2 | 2.1 | 35 | 4910 | 0,0366 | 3.5 | 835 | 780 |
1×630 | 2.4 | 2.2 | 40 | 6220 | 0,0283 | 3.5 | 960 | 880 |
1×800 | 2.6 | 2.4 | 45 | 7870 | 0,0221 | 3.5 | 1110 | 970 |
1×1000 | 2.8 | 2.6 | 51 | 9804 | 0,0176 | 3.5 | 1230 | 1060 |
2 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
2×2.5 | 0.7 | 1.8 | 11.8 | 151 | 7.41 | 3.5 | 26 | 35 |
2×4 | 0.7 | 1.8 | 12.7 | 198 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1.8 | 13.7 | 250 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1.8 | 15 | 374 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1.8 | 17 | 518 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1.8 | 20 | 772 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1.8 | 22 | 1006 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1.8 | 20 | 1365 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1.8 | 21 | 1872 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.8 | 24 | 2475 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 1.8 | 27 | 3089 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 1.9 | 30 | 3834 | 0.124 | 3.5 | 325 | 345 |
3 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×1.5 | 0.7 | 1.5 | 10 | 145 | 12.1 | 3.5 | 20 | 27 |
3×2.5 | 0.7 | 1.5 | 11 | 185 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1.5 | 12 | 250 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1.5 | 13 | 320 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1.8 | 16 | 450 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1.8 | 18 | 640 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1.8 | 21 | 940 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1.8 | 23 | 1260 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1.8 | 23 | 1670 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1.8 | 26 | 2280 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 1.9 | 30 | 3020 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 2 | 32 | 3790 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 2.2 | 37 | 4750 | 0.124 | 3.5 | 325 | 345 |
3×185 | 1.6 | 2.3 | 41 | 5654 | 0,0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 2.4 | 46 | 7243 | 0,0754 | 3.5 | 440 | 450 |
3×300 | 1.8 | 2.6 | 51 | 9465 | 0,0601 | 3.5 | 505 | 515 |
3×400 | 2 | 3 | 64 | 12066 | 0.047 | 3.5 | 570 | 575 |
4 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
4×4 | 0.7 | 1.8 | 13 | 253 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1.8 | 14 | 337 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1.8 | 17 | 501 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1.8 | 20 | 778 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1.8 | 23 | 1160 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1.8 | 25 | 1554 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1.8 | 23 | 2148 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1.8 | 27 | 2928 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.9 | 31 | 3854 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 2 | 33 | 4925 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 2.2 | 38 | 6238 | 0.124 | 3.5 | 325 | 345 |
4×185 | 1.6 | 2.3 | 42 | 7562 | 0,0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 2.5 | 47 | 9836 | 0,0754 | 3.5 | 440 | 450 |
4×300 | 1.8 | 2.6 | 52 | 12550 | 0,0601 | 3.5 | 505 | 515 |
4×400 | 2 | 3.1 | 66 | 15929 | 0.047 | 3.5 | 570 | 575 |
5 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
5×4 | 0.7 | 1.8 | 14.5 | 349 | 4.61 | 3.5 | 34 | 45 |
5×6 | 0.7 | 1.8 | 15.8 | 460 | 3.08 | 3.5 | 43 | 57 |
5×10 | 0.7 | 1.8 | 19 | 699 | 1.83 | 3.5 | 60 | 77 |
5×16 | 0.7 | 1.8 | 22 | 1013 | 1.15 | 3.5 | 83 | 105 |
5×25 | 0.9 | 1.8 | 25 | 1566 | 0.727 | 3.5 | 105 | 125 |
5×35 | 0.9 | 1.9 | 28 | 2083 | 0.524 | 3.5 | 125 | 155 |
5×50 | 1 | 2 | 31 | 2921 | 0.387 | 3.5 | 160 | 185 |
5×70 | 1.1 | 2.1 | 36 | 3974 | 0.268 | 3.5 | 200 | 225 |
5×95 | 1.1 | 2.2 | 39 | 5297 | 0.193 | 3.5 | 245 | 270 |
5×120 | 1.2 | 2.4 | 44 | 6638 | 0.153 | 3.5 | 285 | 310 |
5×150 | 1.4 | 2.5 | 49 | 8290 | 0.124 | 3.5 | 325 | 345 |
5×185 | 1.6 | 2.7 | 55 | 10215 | 0,0991 | 3.5 | 375 | 390 |
5×240 | 1.7 | 3 | 64 | 13130 | 0,0754 | 3.5 | 440 | 450 |
5×300 | 1.8 | 3.2 | 70 | 16670 | 0,0601 | 3.5 | 505 | 515 |
Kabel Daya 3+1 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×4+1×2.5 | 0.7 | 1.8 | 13 | 236 | 4.61 | 3.5 | 34 | 45 |
3×6+1×4 | 0.7 | 1.8 | 14 | 316 | 3.08 | 3.5 | 43 | 57 |
3×10+1×6 | 0.7 | 1.8 | 17 | 461 | 1.83 | 3.5 | 60 | 77 |
3×16+1×10 | 0.7 | 1.8 | 19 | 679 | 1.15 | 3.5 | 83 | 105 |
3×25+1×16 | 0.9 | 1.8 | 22 | 1065 | 0.727 | 3.5 | 105 | 125 |
3×35+1×16 | 0.9 | 1.8 | 24 | 1360 | 0.524 | 3.5 | 125 | 155 |
3×50+1×25 | 1 | 1.8 | 25 | 1901 | 0.387 | 3.5 | 160 | 185 |
3×70+1×35 | 1.1 | 1.9 | 28 | 2585 | 0.268 | 3.5 | 200 | 225 |
3×95+1×50 | 1.1 | 2 | 32 | 3518 | 0.193 | 3.5 | 245 | 270 |
3×120+1×70 | 1.2 | 2.1 | 35 | 4443 | 0.153 | 3.5 | 285 | 310 |
3×150+1×70 | 1.4 | 2.2 | 40 | 5326 | 0.124 | 3.5 | 325 | 345 |
3×185+1×95 | 1.6 | 2.4 | 43 | 8501 | 0,0991 | 3.5 | 375 | 390 |
3×240+1×120 | 1.7 | 2.5 | 48 | 11155 | 0,0754 | 3.5 | 440 | 450 |
3×300+1×150 | 1.8 | 2.7 | 54 | 14470 | 0,0601 | 3.5 | 505 | 515 |
3×400+1×240 | 2 | 3.1 | 66 | 309 | 0.047 | 3.5 | 570 | 575 |
Kabel Daya 3+2 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×4+2×2.5 | 0.7 | 1.8 | 13.9 | 413 | 4.61 | 3.5 | 34 | 45 |
3×6+2×4 | 0.7 | 1.8 | 15.3 | 6682 | 3.08 | 3.5 | 43 | 57 |
3×10+2×6 | 0.7 | 1.8 | 18 | 603 | 1.83 | 3.5 | 60 | 77 |
3×16+2×10 | 0.7 | 1.8 | 21 | 888 | 1.15 | 3.5 | 83 | 105 |
3×25+2×16 | 0.9 | 1.8 | 24 | 1342 | 0.727 | 3.5 | 105 | 125 |
3×35+2×16 | 0.9 | 1.8 | 26 | 1647 | 0.524 | 3.5 | 125 | 155 |
3×50+2×35 | 1 | 1.9 | 29 | 2386 | 0.387 | 3.5 | 160 | 185 |
3×70+2×35 | 1.1 | 2 | 32 | 3201 | 0.268 | 3.5 | 200 | 225 |
3×95+2×50 | 1.1 | 2.1 | 36 | 4269 | 0.193 | 3.5 | 245 | 270 |
3×120+2×70 | 1.2 | 2.3 | 41 | 5437 | 0.153 | 3.5 | 285 | 310 |
3×150+2×70 | 1.4 | 2.4 | 44 | 6519 | 0.124 | 3.5 | 325 | 345 |
3×185+2×95 | 1.6 | 2.5 | 49 | 8101 | 0,0991 | 3.5 | 375 | 390 |
3×240+2×120 | 1.7 | 2.7 | 54 | 10340 | 0,0754 | 3.5 | 440 | 450 |
3×300+2×150 | 1.8 | 2.8 | 56 | 12810 | 0,0601 | 3.5 | 505 | 515 |
Kabel Daya 4+1 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
4×4+1×2.5 | 0.7 | 1.8 | 14.5 | 331 | 4.61 | 3.5 | 34 | 45 |
4×6+1×4 | 0.7 | 1.8 | 15.9 | 435 | 3.08 | 3.5 | 43 | 57 |
4×10+1×6 | 0.7 | 1.8 | 18 | 649 | 1.83 | 3.5 | 60 | 77 |
4×16+1×10 | 0.7 | 1.8 | 21 | 965 | 1.15 | 3.5 | 83 | 105 |
4×25+1×16 | 0.9 | 1.8 | 25 | 1456 | 0.727 | 3.5 | 105 | 125 |
4×35+1×16 | 0.9 | 1.8 | 27 | 1863 | 0.524 | 3.5 | 125 | 155 |
4×50+1×25 | 1 | 1.9 | 29 | 2633 | 0.387 | 3.5 | 160 | 185 |
4×70+1×35 | 1.1 | 2 | 32 | 3565 | 0.268 | 3.5 | 200 | 225 |
4×95+1×50 | 1.1 | 2.1 | 36 | 4735 | 0.193 | 3.5 | 245 | 270 |
4×120+1×70 | 1.2 | 2.3 | 41 | 5977 | 0.153 | 3.5 | 285 | 310 |
4×150+1×70 | 1.4 | 2.4 | 44 | 7276 | 0.124 | 3.5 | 325 | 345 |
4×185+1×95 | 1.6 | 2.5 | 49 | 9055 | 0,0991 | 3.5 | 375 | 390 |
4×240+1×120 | 1.7 | 2.7 | 54 | 11567 | 0,0754 | 3.5 | 440 | 450 |
4×300+1×150 | 1.8 | 3.1 | 66 | 14321 | 0,0601 | 3.5 | 505 | 515 |
Kanggo kerep nambah proses manajemen miturut aturan sampeyan "murni, agama sing apik lan kualitas sing apik minangka basis pangembangan perusahaan", kita nemen nyerep inti saka solusi sing gegandhengan sacara internasional, lan kanthi rutin ngasilake barang anyar kanggo nyukupi kabutuhan para pembeli. Sampel gratis kanggo Kabel Daya Tahan Api Tahan Api lan Kabel Daya Unarmoured, Kita njaga jadwal pangiriman sing pas, desain modern, kualitas lan transparansi kanggo para klien.Moto kita bakal menehi solusi kualitas dhuwur ing wektu sing ditemtokake.
Sampel gratis kanggoChina PVC Insulated Power Cable lan Fire-Resistant Power Cable, Pabrik kita dilengkapi fasilitas lengkap ing 10000 meter persegi, sing ndadekake kita bisa gawe marem prodhuksi lan dodolan kanggo solusi bagean otomatis.Kauntungan kita yaiku kategori lengkap, kualitas dhuwur lan rega sing kompetitif!Adhedhasar iku, barang-barang kita entuk pujian sing dhuwur ing omah lan ing luar negeri.