Kita bakal nggawe saben kerja keras dadi apik banget lan apik banget, lan nyepetake langkah-langkah kanggo ngadeg saka pangkat perusahaan kelas paling dhuwur lan teknologi tinggi kanthi rega Murah 0.6 / 1kv Cu Core XLPE PVC Insulation Power Cable for Construction, " Nggawe Produk lan solusi Kualitas Gedhe" bisa uga dadi tujuan langgeng organisasi kita.Kita nggawe upaya tanpa wates kanggo ngerteni maksud "Kita Bakal Tansah Selaras karo Kabeh Wektu".
Kita bakal nggawe saben kerja keras dadi apik lan apik banget, lan nyepetake langkah-langkah kanggo ngadeg saka pangkat perusahaan kelas paling dhuwur lan teknologi tinggi antar benua kanggoKabel PVC China lan Kabel Daya PVC, Departemen R&D kita tansah ngrancang karo gagasan fashion anyar supaya kita bisa introduce gaya fashion up-to-date saben sasi.Sistem manajemen produksi sing ketat tansah njamin barang sing stabil lan berkualitas.Tim perdagangan kita nyedhiyakake layanan sing tepat wektu lan efisien.Yen ana kapentingan lan pitakonan babagan produk kita, sampeyan kudu hubungi kita ing wektu.Kita pengin nggawe hubungan bisnis karo perusahaan sing diajeni.
Aplikasi
Trunking kabel njero ruangan, njaba kanggo stasiun listrik, industri lan switchgear uga kanggo jaringan pasokan kutha, yen karusakan mekanis ora mungkin.
Konstruksi
Karakteristik
Dirating voltase: 0.6/1kV
1. sak operasi normal kabel, suhu konduktor maksimum kudu 70 ℃ kanggo PVC jampel lan 90 ℃ kanggo XLPE jampel.
2. Suhu maksimum konduktor sajrone sirkuit cendhak (durasi maksimal ora ngluwihi 5 detik): Insulasi PVC - 160 ℃ kanggo bagean konduktor ≤300mm2, 140 ℃ kanggo bagean salib konduktor> 300mm2;Crosslinked PVC insulasi ing 250 ℃.
3. Nalika mbikak kabel, suhu sekitar ora bakal kurang saka 0 ℃, lan minimal allowable mlengkung radius minangka nderek:
Kabel inti tunggal: 20D tanpa lapis baja, 15D lapis baja
Kabel multi-inti: 15D kanggo unarmored, 12D kanggo armored
Where: D- diameteripun njaba kabel.
4. Kabel putus gaya:
Kabel inti aluminium: 40 × S (N)
Kabel inti tembaga: 70 × S (N)
Cathetan: S yaiku total area cross-sectional konduktor
Standar
IEC 60502-1, GB/T 12706.1
Paramèter
Kabel Daya Inti Tunggal | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
1×1.5 | 0.7 | 1.4 | 6 | 53 | 12.1 | 3.5 | 22 | 33 |
1×2.5 | 0.7 | 1.4 | 6 | 68 | 7.41 | 3.5 | 31 | 43 |
1×4 | 0.7 | 1.4 | 7 | 87 | 4.61 | 3.5 | 41 | 56 |
1×6 | 0.7 | 1.4 | 7 | 110 | 3.08 | 3.5 | 52 | 70 |
1×10 | 0.7 | 1.4 | 8 | 155 | 1.83 | 3.5 | 71 | 94 |
1×16 | 0.7 | 1.4 | 9 | 220 | 1.15 | 3.5 | 92 | 120 |
1×25 | 0.9 | 1.4 | 10 | 345 | 0.727 | 3.5 | 120 | 155 |
1×35 | 0.9 | 1.4 | 12 | 424 | 0.524 | 3.5 | 150 | 185 |
1×50 | 1 | 1.4 | 13 | 555 | 0.387 | 3.5 | 180 | 220 |
1×70 | 1.1 | 1.4 | 14 | 770 | 0.268 | 3.5 | 230 | 270 |
1×95 | 1.1 | 1.5 | 16 | 1040 | 0.193 | 3.5 | 285 | 320 |
1×120 | 1.2 | 1.5 | 18 | 1290 | 0.153 | 3.5 | 335 | 365 |
1×150 | 1.4 | 1.6 | 20 | 1590 | 0.124 | 3.5 | 385 | 410 |
1×185 | 1.6 | 1.6 | 22 | 1944 | 0,0991 | 3.5 | 450 | 465 |
1×240 | 1.7 | 1.7 | 25 | 2510 | 0,0754 | 3.5 | 535 | 540 |
1×300 | 1.8 | 1.8 | 27 | 3042 | 0,0601 | 3.5 | 620 | 610 |
1×400 | 2 | 1.9 | 31 | 3869 | 0.047 | 3.5 | 720 | 695 |
1×500 | 2.2 | 2.1 | 35 | 4910 | 0,0366 | 3.5 | 835 | 780 |
1×630 | 2.4 | 2.2 | 40 | 6220 | 0,0283 | 3.5 | 960 | 880 |
1×800 | 2.6 | 2.4 | 45 | 7870 | 0,0221 | 3.5 | 1110 | 970 |
1×1000 | 2.8 | 2.6 | 51 | 9804 | 0,0176 | 3.5 | 1230 | 1060 |
2 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
2×2.5 | 0.7 | 1.8 | 11.8 | 151 | 7.41 | 3.5 | 26 | 35 |
2×4 | 0.7 | 1.8 | 12.7 | 198 | 4.61 | 3.5 | 34 | 45 |
2×6 | 0.7 | 1.8 | 13.7 | 250 | 3.08 | 3.5 | 43 | 57 |
2×10 | 0.7 | 1.8 | 15 | 374 | 1.83 | 3.5 | 60 | 77 |
2×16 | 0.7 | 1.8 | 17 | 518 | 1.15 | 3.5 | 83 | 105 |
2×25 | 0.9 | 1.8 | 20 | 772 | 0.727 | 3.5 | 105 | 125 |
2×35 | 0.9 | 1.8 | 22 | 1006 | 0.524 | 3.5 | 125 | 155 |
2×50 | 1 | 1.8 | 20 | 1365 | 0.387 | 3.5 | 160 | 185 |
2×70 | 1.1 | 1.8 | 21 | 1872 | 0.268 | 3.5 | 200 | 225 |
2×95 | 1.1 | 1.8 | 24 | 2475 | 0.193 | 3.5 | 245 | 270 |
2×120 | 1.2 | 1.8 | 27 | 3089 | 0.153 | 3.5 | 285 | 310 |
2×150 | 1.4 | 1.9 | 30 | 3834 | 0.124 | 3.5 | 325 | 345 |
3 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×1.5 | 0.7 | 1.5 | 10 | 145 | 12.1 | 3.5 | 20 | 27 |
3×2.5 | 0.7 | 1.5 | 11 | 185 | 7.41 | 3.5 | 26 | 35 |
3×4 | 0.7 | 1.5 | 12 | 250 | 4.61 | 3.5 | 34 | 45 |
3×6 | 0.7 | 1.5 | 13 | 320 | 3.08 | 3.5 | 43 | 57 |
3×10 | 0.7 | 1.8 | 16 | 450 | 1.83 | 3.5 | 60 | 77 |
3×16 | 0.7 | 1.8 | 18 | 640 | 1.15 | 3.5 | 83 | 105 |
3×25 | 0.9 | 1.8 | 21 | 940 | 0.727 | 3.5 | 105 | 125 |
3×35 | 0.9 | 1.8 | 23 | 1260 | 0.524 | 3.5 | 125 | 155 |
3×50 | 1 | 1.8 | 23 | 1670 | 0.387 | 3.5 | 160 | 185 |
3×70 | 1.1 | 1.8 | 26 | 2280 | 0.268 | 3.5 | 200 | 225 |
3×95 | 1.1 | 1.9 | 30 | 3020 | 0.193 | 3.5 | 245 | 270 |
3×120 | 1.2 | 2 | 32 | 3790 | 0.153 | 3.5 | 285 | 310 |
3×150 | 1.4 | 2.2 | 37 | 4750 | 0.124 | 3.5 | 325 | 345 |
3×185 | 1.6 | 2.3 | 41 | 5654 | 0,0991 | 3.5 | 375 | 390 |
3×240 | 1.7 | 2.4 | 46 | 7243 | 0,0754 | 3.5 | 440 | 450 |
3×300 | 1.8 | 2.6 | 51 | 9465 | 0,0601 | 3.5 | 505 | 515 |
3×400 | 2 | 3 | 64 | 12066 | 0.047 | 3.5 | 570 | 575 |
4 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
4×4 | 0.7 | 1.8 | 13 | 253 | 4.61 | 3.5 | 34 | 45 |
4×6 | 0.7 | 1.8 | 14 | 337 | 3.08 | 3.5 | 43 | 57 |
4×10 | 0.7 | 1.8 | 17 | 501 | 1.83 | 3.5 | 60 | 77 |
4×16 | 0.7 | 1.8 | 20 | 778 | 1.15 | 3.5 | 83 | 105 |
4×25 | 0.9 | 1.8 | 23 | 1160 | 0.727 | 3.5 | 105 | 125 |
4×35 | 0.9 | 1.8 | 25 | 1554 | 0.524 | 3.5 | 125 | 155 |
4×50 | 1 | 1.8 | 23 | 2148 | 0.387 | 3.5 | 160 | 185 |
4×70 | 1.1 | 1.8 | 27 | 2928 | 0.268 | 3.5 | 200 | 225 |
4×95 | 1.1 | 1.9 | 31 | 3854 | 0.193 | 3.5 | 245 | 270 |
4×120 | 1.2 | 2 | 33 | 4925 | 0.153 | 3.5 | 285 | 310 |
4×150 | 1.4 | 2.2 | 38 | 6238 | 0.124 | 3.5 | 325 | 345 |
4×185 | 1.6 | 2.3 | 42 | 7562 | 0,0991 | 3.5 | 375 | 390 |
4×240 | 1.7 | 2.5 | 47 | 9836 | 0,0754 | 3.5 | 440 | 450 |
4×300 | 1.8 | 2.6 | 52 | 12550 | 0,0601 | 3.5 | 505 | 515 |
4×400 | 2 | 3.1 | 66 | 15929 | 0.047 | 3.5 | 570 | 575 |
5 Kabel Daya Inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
5×4 | 0.7 | 1.8 | 14.5 | 349 | 4.61 | 3.5 | 34 | 45 |
5×6 | 0.7 | 1.8 | 15.8 | 460 | 3.08 | 3.5 | 43 | 57 |
5×10 | 0.7 | 1.8 | 19 | 699 | 1.83 | 3.5 | 60 | 77 |
5×16 | 0.7 | 1.8 | 22 | 1013 | 1.15 | 3.5 | 83 | 105 |
5×25 | 0.9 | 1.8 | 25 | 1566 | 0.727 | 3.5 | 105 | 125 |
5×35 | 0.9 | 1.9 | 28 | 2083 | 0.524 | 3.5 | 125 | 155 |
5×50 | 1 | 2 | 31 | 2921 | 0.387 | 3.5 | 160 | 185 |
5×70 | 1.1 | 2.1 | 36 | 3974 | 0.268 | 3.5 | 200 | 225 |
5×95 | 1.1 | 2.2 | 39 | 5297 | 0.193 | 3.5 | 245 | 270 |
5×120 | 1.2 | 2.4 | 44 | 6638 | 0.153 | 3.5 | 285 | 310 |
5×150 | 1.4 | 2.5 | 49 | 8290 | 0.124 | 3.5 | 325 | 345 |
5×185 | 1.6 | 2.7 | 55 | 10215 | 0,0991 | 3.5 | 375 | 390 |
5×240 | 1.7 | 3 | 64 | 13130 | 0,0754 | 3.5 | 440 | 450 |
5×300 | 1.8 | 3.2 | 70 | 16670 | 0,0601 | 3.5 | 505 | 515 |
Kabel Daya 3+1 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×4+1×2.5 | 0.7 | 1.8 | 13 | 236 | 4.61 | 3.5 | 34 | 45 |
3×6+1×4 | 0.7 | 1.8 | 14 | 316 | 3.08 | 3.5 | 43 | 57 |
3×10+1×6 | 0.7 | 1.8 | 17 | 461 | 1.83 | 3.5 | 60 | 77 |
3×16+1×10 | 0.7 | 1.8 | 19 | 679 | 1.15 | 3.5 | 83 | 105 |
3×25+1×16 | 0.9 | 1.8 | 22 | 1065 | 0.727 | 3.5 | 105 | 125 |
3×35+1×16 | 0.9 | 1.8 | 24 | 1360 | 0.524 | 3.5 | 125 | 155 |
3×50+1×25 | 1 | 1.8 | 25 | 1901 | 0.387 | 3.5 | 160 | 185 |
3×70+1×35 | 1.1 | 1.9 | 28 | 2585 | 0.268 | 3.5 | 200 | 225 |
3×95+1×50 | 1.1 | 2 | 32 | 3518 | 0.193 | 3.5 | 245 | 270 |
3×120+1×70 | 1.2 | 2.1 | 35 | 4443 | 0.153 | 3.5 | 285 | 310 |
3×150+1×70 | 1.4 | 2.2 | 40 | 5326 | 0.124 | 3.5 | 325 | 345 |
3×185+1×95 | 1.6 | 2.4 | 43 | 8501 | 0,0991 | 3.5 | 375 | 390 |
3×240+1×120 | 1.7 | 2.5 | 48 | 11155 | 0,0754 | 3.5 | 440 | 450 |
3×300+1×150 | 1.8 | 2.7 | 54 | 14470 | 0,0601 | 3.5 | 505 | 515 |
3×400+1×240 | 2 | 3.1 | 66 | 309 | 0.047 | 3.5 | 570 | 575 |
Kabel Daya 3+2 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
3×4+2×2.5 | 0.7 | 1.8 | 13.9 | 413 | 4.61 | 3.5 | 34 | 45 |
3×6+2×4 | 0.7 | 1.8 | 15.3 | 6682 | 3.08 | 3.5 | 43 | 57 |
3×10+2×6 | 0.7 | 1.8 | 18 | 603 | 1.83 | 3.5 | 60 | 77 |
3×16+2×10 | 0.7 | 1.8 | 21 | 888 | 1.15 | 3.5 | 83 | 105 |
3×25+2×16 | 0.9 | 1.8 | 24 | 1342 | 0.727 | 3.5 | 105 | 125 |
3×35+2×16 | 0.9 | 1.8 | 26 | 1647 | 0.524 | 3.5 | 125 | 155 |
3×50+2×35 | 1 | 1.9 | 29 | 2386 | 0.387 | 3.5 | 160 | 185 |
3×70+2×35 | 1.1 | 2 | 32 | 3201 | 0.268 | 3.5 | 200 | 225 |
3×95+2×50 | 1.1 | 2.1 | 36 | 4269 | 0.193 | 3.5 | 245 | 270 |
3×120+2×70 | 1.2 | 2.3 | 41 | 5437 | 0.153 | 3.5 | 285 | 310 |
3×150+2×70 | 1.4 | 2.4 | 44 | 6519 | 0.124 | 3.5 | 325 | 345 |
3×185+2×95 | 1.6 | 2.5 | 49 | 8101 | 0,0991 | 3.5 | 375 | 390 |
3×240+2×120 | 1.7 | 2.7 | 54 | 10340 | 0,0754 | 3.5 | 440 | 450 |
3×300+2×150 | 1.8 | 2.8 | 56 | 12810 | 0,0601 | 3.5 | 505 | 515 |
Kabel Daya 4+1 inti | ||||||||
Nom.Cross-bagean saka konduktor | Ketebalan Isolasi | Ketebalan Sarung | Kira-kira.OD | Kira-kira Bobot | Maks.Resistansi DC Konduktor (20°C) | Tes Tegangan AC | Rating saiki | |
mm2 | mm | mm | mm | kg/km | Ω/km | kV / 5 min | Ing udara (A) | Ing lemah (A) |
4×4+1×2.5 | 0.7 | 1.8 | 14.5 | 331 | 4.61 | 3.5 | 34 | 45 |
4×6+1×4 | 0.7 | 1.8 | 15.9 | 435 | 3.08 | 3.5 | 43 | 57 |
4×10+1×6 | 0.7 | 1.8 | 18 | 649 | 1.83 | 3.5 | 60 | 77 |
4×16+1×10 | 0.7 | 1.8 | 21 | 965 | 1.15 | 3.5 | 83 | 105 |
4×25+1×16 | 0.9 | 1.8 | 25 | 1456 | 0.727 | 3.5 | 105 | 125 |
4×35+1×16 | 0.9 | 1.8 | 27 | 1863 | 0.524 | 3.5 | 125 | 155 |
4×50+1×25 | 1 | 1.9 | 29 | 2633 | 0.387 | 3.5 | 160 | 185 |
4×70+1×35 | 1.1 | 2 | 32 | 3565 | 0.268 | 3.5 | 200 | 225 |
4×95+1×50 | 1.1 | 2.1 | 36 | 4735 | 0.193 | 3.5 | 245 | 270 |
4×120+1×70 | 1.2 | 2.3 | 41 | 5977 | 0.153 | 3.5 | 285 | 310 |
4×150+1×70 | 1.4 | 2.4 | 44 | 7276 | 0.124 | 3.5 | 325 | 345 |
4×185+1×95 | 1.6 | 2.5 | 49 | 9055 | 0,0991 | 3.5 | 375 | 390 |
4×240+1×120 | 1.7 | 2.7 | 54 | 11567 | 0,0754 | 3.5 | 440 | 450 |
4×300+1×150 | 1.8 | 3.1 | 66 | 14321 | 0,0601 | 3.5 | 505 | 515 |
Kita bakal nggawe saben kerja keras dadi apik banget lan apik banget, lan nyepetake langkah-langkah kanggo ngadeg saka pangkat perusahaan kelas paling dhuwur lan teknologi tinggi kanthi rega Murah 0.6 / 1kv Cu Core XLPE PVC Insulation Power Cable for Construction, " Nggawe Produk lan solusi Kualitas Gedhe" bisa uga dadi tujuan langgeng organisasi kita.Kita nggawe upaya tanpa wates kanggo ngerteni maksud "Kita Bakal Tansah Selaras karo Kabeh Wektu".
Regane murahKabel PVC China lan Kabel Daya PVC, Departemen R&D kita tansah ngrancang karo gagasan fashion anyar supaya kita bisa introduce gaya fashion up-to-date saben sasi.Sistem manajemen produksi sing ketat tansah njamin barang sing stabil lan berkualitas.Tim perdagangan kita nyedhiyakake layanan sing tepat wektu lan efisien.Yen ana kapentingan lan pitakonan babagan produk kita, sampeyan kudu hubungi kita ing wektu.Kita pengin nggawe hubungan bisnis karo perusahaan sing diajeni.